armaprotect-fw1.png

ArmaProtect™ FW1

ArmaProtect™ FW1 is a flexible, fabric-based firestop wrap engineered to restore and maintain the fire-resistance rating of walls and floors at service penetrations. Constructed from a glass filament fabric composite with a specialized intumescent coating on both the inside and outside, it provides firestopping for combustible/non-combustible pipes, conduit bundles, and cable runs.

When exposed to heat during a fire event, the coating reacts and expands to form an insulating seal that closes off annular gaps and crushes collapsing pipes, preventing the spread of flames, smoke, and toxic gases.

Key Features & Benefits

  • High Fire Resistance: Tested and certified under international standards, offering UL-approved FT-Ratings up to 3 hours (ANSI/UL 1479 / ASTM E814) and European Technical Assessments (ETA under EN 1366-3).
  • Flexible & Tear-Resistant: Highly pliable design makes it easy to cut, shape, and wrap snugly around various pipe sizes and complex conduit/cable bundles.
  • Durable Construction: Built with glass filament fabric for high mechanical strength and long-term durability.
  • Weather & Environmental Resistance: Rated Type X (EOTA TR 024) for resistance against weathering and broad operating temperatures (-40°C to 70°C (-40°F to 158°F)).
  • Safe & Sustainable: Halogen-free and free of dangerous substances for safe indoor installation and handling.

Technical Specifications Summary

Feature Specification
Material Base Glass filament fabric composite with intumescent insulating coating
Color Red (outside) / Anthracite dark grey (inside)
Dimensions (Roll) 10m length x 100mm width x 1.5mm thickness
Operating Temp. -40°C to 70°C (-40°F to 158°F)
Processing Temp. 5°C to 25°C (41°F to 77°F)
Reaction to Fire Class E (EN 13501-1)
Certifications UL 1479 / ASTM E814 (up to 3 hrs), ETA-22/0063, ETA-22/0064

PRODUCT BROCHURE  

Primary Applications

  • Pipe Penetrations: Sealing non-combustible pipes (steel, copper) up to dia <323.9mm with combustible thermal insulation, as well as plastic/composite pipes.
  • Cable & Conduit Runs: Firestopping single cables, cable bundles, cable trays, conduits, and conduit bundles passing through fire-rated walls and floors.
  • Wall & Floor Penetrations: Compartmentation sealing in flexible walls, solid masonry/concrete walls, and concrete floor slabs.